ELECTRICAL
WIRING REQUIREMENTS FOR STORABLE POOLS
2008 National Electrical
Code / 2010 Residential Code of New York State
STORABLE POOLS ARE THOSE THAT ARE CONSTRUCTED ON OR ABOVE THE GROUND, AND ARE CAPABLE OF HOLDING WATER
TO A MAXIMUM DEPTH OF 42 INCHES (1.0 M), OR A POOL WITH NON METALLIC, MOLDED POLYMERIC WALLS, OR INFLATABLE
FABRIC WALLS REGUARDLESS OF DIMENSION. (The maximum water depth of 42” does not apply to inflatable swimming pools)
1) Storable Pool Pumps
a. A cord-connected pool filter must incorporate an approved system of double insulation or equivalent
b. Cord-connected pool filter pumps must be provided with a ground-fault circuit interrupter (GFCI) that is an integral
part of the attached plug or located in the power supply cord within 12” of the attached plug.
2) Receptacle (Outlet) and Wiring Method for Storable Pool Pump
a. Receptacles cannot be located within 6’ of the inside wall of a storable pool
b. The receptacle must be grounded and must be Ground Fault Circuit Interrupter (GFCI) protected.
c. Receptacle must have a weatherproof cover that can be closed when the cord is plugged in. (In-use type cover)
d. An Automatic Timer (Time Switch) must be installed on storable swimming pool pumps.
3) Luminaries (lights) for Storable Pools (if used)
a. Luminaries cannot have exposed metal parts and must be listed for the purpose
b. Luminaries 15 Volts or Less Must:
i. Have a luminaire lamp that operates at 15 volts or less
ii. Have an impact-resistant polymeric lens, luminaire body, and a transformer enclosure
iii. Have a transformer listed for swimming pools with a primary rating not over 150 volts
c. Luminaries Over 15 Volts But Not Over 150 Volts:
i. Have an impact-resistant polymeric lens and luminaire body
ii. Have Ground Fault Circuit Interrupter (GFCI) protect
4) Other
a. Building Permits are required. Secure a Building Permit prior to beginning work from your municipality
b. Pool Alarms may be required (Check with your local Building Department for additional information)
c. All receptacles located within 20’ of the inside walls of a storable pool wall must be GFCI protected
Check with
your local building department for any additional
requirements and/or restrictions prior to beginning
work
PRINTABLE
VERSION |
| |
|
|
Should
you have questions, problems or
suggestions regarding our web site please contact our WebMaster
[ ABOUT
GHI "HOME"
][ HOME INSPECTION ][ INSPECTION
FEES ][ SET AN APPOINTMENT]
[RADON TESTING ][ PEST
INSPECTIONS ][ CUSTOMER TESTIMONIALS
][ FEATURE TOPICS] [ BROKERS
AND REAL ESTATE AGENTS ][SCHEDULE
APPOINTMENT ON-LINE][CONTACT
US ]
Gunther
Home Inspections, Inc.
Voice 585-349-3900 - Fax 585-349-3834
2767 Dewey Avenue - Rochester, NY 14616
www.InspectNY.com
©
1998-2011 Gunther Home Inspections, Incorporated